Group 1: | Group 2: | Group 3: | ||||
---|---|---|---|---|---|---|
One or several single stranded conductors layed in tubes. | Multi-stranded conductors, e. g. sheated cable, fish wire, lead-sheated cable, flexible cable. | Single-stranded aerial cable layed at a minimum distance equal to conductor diameter, single stranded wire for switchgear and distributing installations. | ||||
Wire- size |
Fuses | Current- rating |
Fuses | Current- rating |
Fuses | Current- rating |
mm² | A | A | A | A | A | A |
0.75 | 13 | 10 | 16 | 16 | ||
1 | 12 | 10 | 16 | 16 | 20 | 20 |
1.5 | 16 | 16 | 20 | 20 | 25 | 25 |
2.5 | 21 | 20 | 27 | 25 | 34 | 35 |
4 | 27 | 25 | 36 | 35 | 45 | 50 |
6 | 35 | 35 | 47 | 50 | 57 | 63 |
10 | 48 | 50 | 65 | 63 | 78 | 80 |
16 | 65 | 63 | 87 | 80 | 104 | 100 |
25 | 88 | 80 | 115 | 100 | 137 | 125 |
35 | 110 | 100 | 143 | 125 | 168 | 160 |
50 | 140 | 125 | 178 | 160 | 210 | 200 |
70 | 175 | 160 | 220 | 224 | 260 | 250 |
95 | 210 | 200 | 265 | 250 | 310 | 300 |
120 | 250 | 250 | 310 | 300 | 365 | 355 |
150 | 355 | 355 | 415 | 425 | ||
185 | 405 | 355 | 475 | 425 | ||
240 | 480 | 425 | 560 | 500 | ||
300 | 555 | 500 | 645 | 600 | ||
400 | 770 | 710 | ||||
500 | 880 | 850 |